Elix

  • energy efficient EC motor
  • provides low level continuous ventilation to control condensation
  • 3 speed centrifugal fan
  • choice of 2 low speeds at installation
  • for wall or ceiling
  • for any domestic wet room
  • low noise levels and running costs
  • compliant with Building Regulations Parts L1 2010 and F 2010
  • SAP PCDB Listed

General

  • SAP PCDB Listed (dMEV) ultra modern, technically innovative high performance, low noise level fan
  • exhausts directly to the outside or through long lengths of ducting (up to 15m)
  • runs continuously at pre-selected choice of two speeds (fixed at installation)
  • Speed 1 operates at 8.8 l/s (factory set)
  • Speed 2 operates at 13 l/s
  • anti-vibration gasket
  • easily removal, washable polypropylene filter
  • speed boosted to maximum (28 l/s) using integral pull cord or by:
    • remote switch/light switch
    • PIR sensor
    • DRH240 (dynamic remote humidistat)
  • energy saving ventilation
  • extremely low running costs
  • low carbon footprint
  • 5 year warranty
  • Vectaire Ltd can supply all accessories for use with these units, including fire dampers, air valves, ducting, outside grilles and wall cowls. Additionally, Vectaire offers a design service to ensure that the unit installed is the best possible to provide efficient, effective, low energy and low running cost ventilation. Vectaire can also organise installation, commissioning and maintenance of these products
  • These fans are NOT suitable for use with Gravity Grilles. They should be installed using either Cowls or Fixed Grilles. Only approved accessories should be used.


Back to top

Specification

  • shockproof, high quality technopolymer casing
  • designed using latest wind tunnel technology and CFD simulations
  • profile increases the fluid dynamics
  • EC induction motor with thermal protection
  • 30,000 hour life motors with maintenance free and long life ball bearings
  • operates in ambient temperatures up to 40ºC
  • double insulated - no earth required
  • IPX4 - Splashproof rated - can safely be installed in Zones I and II


Back to top

Compliance

  • Part L1A 2013 of Building Regulations for enhanced energy saving capability
  • Part F 2013 of Building Regulations for reliable, efficient ventilation
  • EU RoHS Directive Compliant.
  • Complies with IEC60335-2-80, LVD2006/95/CE and EMC2014/30/UE (European Directive against radio interference and electro-magnetic compatibility
  • CE marked
  • SAP PCDB Listed
  • Energy Saving Trust Best Practice Compliant


Back to top

Range

  • ELX1003 - 3 speed, continuous running, cord or remote
  • ELX1003DT - 3 speed, continuous running with comfort timer (timer does not activate unless fan has been running for 2 minutes to avoid unnecessary night-time operation) and pull-cord
  • ELX1003HDT - 3 speed, continuous running, with comfort timer, humidistat and pull-cord
  • ELX1003LV - 3 speed, continuous running with pull-cord - LOW VOLT (SELV)
  • ELX1003DTLV - 3 speed, continuous running, with comfort timer, overrun timer and pull-cord LOW VOLT (SELV)
  • ELX1003HDTLV - 3 speed, continuous running, with comfort timer, humidistat and pull-cord - LOW VOLT (SELV)
  • ELX1003-F - Elix Filter
  • PLT/EL - EL & ELX Adaptor Plate
  • PLT/EL/UN - EL & ELX Adaptor Plate - Universal Model
  • THESE FANS SHOULD BE INSTALLED WITH EITHER A FIXED GRILLE OR COWL


Back to top

Features

*Air Intake*Elix Filter*Elix Side View


Back to top

Pressure

*


Back to top

Dimensions

*


Back to top

Typical specification

Supply and Install an ELX1003 high performance, energy efficient centrifugal fan which has been tested and is SAP PCDB Listed and suitable for ALL domestic wet rooms as supplied by Vectaire Ltd, Lincoln Road, Cressex Business Park, High Wycombe, Bucks, HP12 3RH. The fan is to be suitable for installation either into a wall or ceiling (with the appropriate accessories) and to have an air intake around the whole perimeter and have a footprint of no more than 180mm square. The fan is to be continuous running at its low speed (with a choice of two lower speeds) and be capable of being boosted to maximum speed by means of an integral pull cord or (with the cord removed) a remote switch, PIR sensor or humidistat. The fan should have specific fan power (as tested by BRE) of no higher than 0.22w/l/s in a kitchen and 0.16w/l/s in a bathroom. The fan must not exceed 2.0w power consumption on the lowest speed. The fan casing should be made of shock-proof, high quality technopolymer, and should have an EC induction motor with maintenance-free, long life ball bearings, and up to a 43,000 hour life. It should be protected with a thermal cut-out. The fan should be double insulated and be lPX4 splashproof protected suitable for installation into Zones I and Il. The fan is to comply with IEC 60335-2-80, LVD2006/95/CE and EMC 2OO4/108/CE European Directive against radio interference and electro-magnetic compatibility, be CE marked. The fan should have 5 year manufacturer’s warranty and be supplied with a user guide as required, and SAP Q Eligible. Only approved accessories should be used: Wall Plates – as required Wall terminations – all wall terminations must use the approved wall cowl or high rise kit.



Back to top